Enter the voltage, current, cable length and wire gauge to see the voltage drop.
Results are estimates for planning. Check the figures before you make a financial or health decision.
Embed this calculator on your website
Free to use. Copy the code and paste it into your page. Please keep the link under the calculator in place: it is how we keep the tool free.
How the calculator works
Voltage drop is the current multiplied by the cable resistance over the whole loop. The calculator uses typical resistance per length for each AWG gauge, with aluminium about 64% higher than copper, and uses a factor of 2 for single-phase and the square root of 3 for three-phase.
It shows the percentage drop, the voltage at the load and the power lost as heat in the cable.
How to use the voltage drop calculator
- Circuit
- Supply voltage
- Current
- Cable length, one way
- Length unit
- Wire gauge (AWG)
- Conductor
The answer updates as you type, so you can change a value and see the result straight away. Every result shows the main figure first, then the detail behind it.
Worked example
Using the default values:
| Input | Value |
|---|---|
| Circuit | DC or single-phase AC |
| Supply voltage | 230 volts |
| Current | 16 amps |
| Cable length, one way | 30 |
| Length unit | Metres |
| Wire gauge (AWG) | 12 AWG |
| Conductor | Copper |
Voltage drop: 6.24 V (2.71%)
| Result | Value |
|---|---|
| Voltage at the load | 223.76 V |
| Assessment | Within the common 3% guide |
| Cable resistance, one way | 0.1949 Ω |
| Power lost in the cable | 99.8 W |
Tips
A drop of 3% or less is a common guide for a branch circuit. Check local wiring rules and the manufacturer’s data before installing.
Frequently asked questions
How much voltage drop is acceptable?
A common guide is 3% for a circuit and 5% for the whole installation.
How do I reduce voltage drop?
Use a thicker cable, a shorter run or a higher voltage.
Why does length matter?
Resistance rises with cable length, so a longer run drops more voltage.